What is your minimum order quantity (MOQ)?

For anti-static panels the MOQ is 10 m² for samples and trial orders. For bare OA panels and pre-finished floors the MOQ is 50 m². A 20 GP container holds roughly 400–600 m² depending on panel type and thickness.

What are your payment and delivery terms?

We work with T/T and L/C. Delivery is typically 10 days for Asia, 20 days for North America and Australia, and 30 days for Europe, the Middle East, Africa, South America and Russia. Contracts can be FOB, CFR or CIF.

Product

What is the difference between the two product families — anti-static and bare finish?

Anti-static Raised Floor is the finished computer-room floor: the panel arrives with a conductive HPL, PVC or ceramic surface and a guaranteed system resistance of 1 × 10⁶ – 1 × 10⁹ Ω, so it is ready for equipment the day it is laid. Bare Finish Raised Floor (our OA range) is the same structural idea delivered unfinished — the project carpet, PVC, wood or stone is laid on site or bonded in our factory. It is the standard choice for offices, casinos and hotels, where appearance matters more than ESD control.

Which core material should I choose — steel, calcium sulphate, aluminium or wood?

Steel-cement is the economical workhorse with high strength and short lead times. Calcium sulphate gives a non-combustible Class A core with better acoustics and is preferred in European data centres. Solid die-cast aluminium is for corrosive or humidity-critical sites and where weight matters. Wood core is the light, warm and economical option for offices and schools.

Which covering should I choose — HPL, PVC or ceramic tile?

HPL is the most popular: economical, wear resistant and available in twelve decors. Conductive PVC gives seamless joints and comfortable walking for workshops and clean rooms. ESD ceramic tile offers a premium porcelain look with extreme durability for control centres and public areas.

Technical

What loading class do I need for my project?

Most data centres use panels with concentrated load ≥ 2950–4450 N; heavy equipment aisles need 5560–6665 N. Offices with normal furniture are fine at 2500–4450 N, while casino gaming floors with dense slot banks should use ≥ 4450 N. Send us your equipment layout and our engineers will verify the class and optimise panel distribution free of charge.

Do you provide CAD drawings and installation guidance?

Yes. We provide complete CAD installation details, optimise the panel layout for special applications, and can appoint technical installation supervisors to guide installation on site anywhere in the world.

How is anti-static performance measured and maintained?

Our panels measure a system resistance of 1 × 10⁶ – 1 × 10⁹ Ω per ANSI/ESD S20.20 and SJ/T 10796. The performance is permanent: it is built into the covering material, not a surface treatment, and requires no re-application.

Can a bare floor be finished on site, or must it be pre-bonded in the factory?

Both are possible. Site-laid finishes (carpet tiles, sheet PVC) are cheaper and let the interior contractor control the final look, but joints run along panel edges. Factory pre-bonding guarantees the pattern lines up across every panel, needs no adhesive or curing on site, and is the better choice for fast-track and occupied buildings.